EA2-B0-24-450-12A-CB [Carling Technologies]

Circuit Breaker; 断路器
EA2-B0-24-450-12A-CB
型号: EA2-B0-24-450-12A-CB
厂家: Carling Technologies    Carling Technologies
描述:

Circuit Breaker
断路器

断路器
文件: 总9页 (文件大小:3238K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
E-Series  
Circuit Breaker  
The E-Series hydraulic/magnetic circuit breaker is ideally suited  
for higher current and voltage applications. It is UL listed  
and CSA certified for branch circuit protection, which does  
not require a fuse back up. It is also UL recognized and CSA  
certified as a supplementary protector and as a manual motor  
controller.  
Its physical features include front and back mounting, screw  
and stud terminals and heavy duty box wire connectors  
for solid wire or a pressure plate connector for standard  
wire.The E-series is available with handle actuators and can  
be configured as .1-125 amps, up to 600VAC or 125VDC,  
with choice of time delays, actuator colors and 1 to 6 poles  
configuration. Additionally, a Power Selector device is also  
available.  
Typical Applications:  
Š
Š
Š
Š
Š
Ideal for higher current and voltage applications  
Renewable energy systems  
Military  
Product Highlights:  
Š
UL listed and CSA certified  
Š
Certified for circuit branch protection  
Š
Industrial controls  
Recognized as a supplementary protector and as a manual  
Generators  
motor controller  
Š
Optional Power Selector Device  
Carling Technologies, Inc.  
60 Johnson Avenue • Plainville, CT 06062-1177  
Phone: (860) 793-9281 • Fax: (860) 793-9231  
Email: sales@carlingtech.com • www.carlingtech.com  
|
2
E-Series Circuit Breaker - General Specifications  
Mechanical  
Electrical  
Endurance  
6,000 ON-OFF operations @ 6 per  
minute; with rated Current and Voltage.  
Additional 4,000 ON-OFF mechanical.  
All E-Series Circuit Breakers will trip on  
overload, even when Handle is forcibly  
held in the ON position.  
The operating Handle moves positively  
to the OFF position when an overload  
causes the breaker to trip.  
Maximum Voltage  
Current Ratings  
600VAC 50/60 Hz, 125VDC (Table A)  
Standard current coils: 0.100, 0.250,  
0.500, 1.00, 2.50, 5.00, 7.50, 10.0, 15.0,  
20.0, 25.0, 30.0, 50.0, 60.0, 70.0, 100 &  
125 Amp.  
Trip Free  
Auxiliary Switch Rating SPDT; 10.1A 250VAC, 1.0A 65VDC;  
0.5A 80VDC, 0.1A 125VAC (with gold  
contacts).  
Insulation Resistance  
Dielectric Strength  
Trip Indication  
Minimum of 100 Megohms at 500 VDC.  
UL, CSA: 2200 V 50/60 Hz for one  
minute between all electrically isolated  
terminals. E-Series Circuit Breakers  
comply with the 8mm spacing and  
3750V 50/60 Hz dielectric requirements  
from hazardous voltage to operator  
accessible surfaces, between adjacent  
poles and from main circuits to  
Physical  
Number of Poles  
Mounting  
1 - 6  
A 3” minimum spacing must be  
provided between the circuit breaker  
arc venting area on back connected  
E-Series circuit breakers and grounded  
obstructions. E-Series circuit breakers  
must be mounted on a vertical surface.  
auxiliary circuits per Publications EN  
60950 and VDE 0805.  
Connectors, Box Type Front connected E-Series circuit  
breakers are supplied with box type  
pressure connectors that accept  
copper or aluminum conductors  
as follows: 1/0-14 Copper, 1/0-12  
Aluminum.  
Resistance, Impedance Values from Line to Load Terminal -  
based on Series Trip Circuit Breaker.  
Internal Circuit  
Configuration  
Series and Switch Only, (with or without  
auxiliary switch). Shunt with current  
coils.  
Weight  
Approximately 252 grams/pole  
(Approximately 9 ounces/pole)  
Housing-Black; Actuator - See Ordering  
Scheme.  
Standard Colors  
Environmental  
Designed in accordance with requirements of specification  
MIL PRF-55629 & MIL-STD-202G as follows:  
Shock  
Withstands 100 Gs, 6ms, sawtooth while  
carrying rated current per Method 213,  
Test Condition “I”.  
Withstands 0.060” excursion from  
10-55 Hz, and 10 Gs 55-500 Hz, at  
rated current per Method 204C, Test  
Condition A.  
Pulse Tolerance Curves  
Vibration  
Moisture Resistance  
Salt Spray  
Method 106D, i.e., ten 24-hour cycles @  
+ 25°C to +65°C, 80-98% RH.  
Method 101, Condition A (90-95% RH @  
5% NaCl Solution, 96 hrs).  
Method 107D, Condition A (Five cycles  
@ -55°C to +25°C to +85°C to +25°C).  
Thermal Shock  
Operating Temperature -40° C to +85° C  
*Manufacturer reserves the right to change product specification without prior notice.  
60 Johnson Avenue • Plainville, CT 06062–1177 • Phone: (860) 793–9281 • Fax: (860) 793–9231  
Email: sales@carlingtech.com • www.carlingtech.com  
|
E-Series Circuit Breaker - General Specifications  
3
Agency Certifications  
Component Supplementary  
Protector (Class 3215 30, File  
047848 0 000)  
UL Recognized  
CSA Accepted  
Component Recognition Program  
UL Standard 1077  
as Protectors, Supplementary  
(Guide QVNU2, File E75596)  
CSA Standard C22.2 No. 235  
Component Recognition Program  
as Manual Motor Controls (Guide  
NLRV2, File E135367)  
Circuit Breaker Molded Case  
(Class 1432 01, File 093910),  
CSA Standard C22.2 No. 5.1 - M  
CSA Certified  
TUV Certified  
VDE Certified  
Protectors, Supplementary for  
Marine Electrical & Fuel Systems  
(Guide PEQZ2, File E75596)  
Ignition Protection  
EN60934 under License No.  
R72031056  
UL Standard 1500  
EN60934, VDE 0642 under File  
No. 10537  
UL Listed  
UL Standard 489  
Circuit Breakers, Molded Case  
(Guide DIVQ, File E129899)  
Electrical Tables  
Table A: Lists UL Listed (489) & CSA Certified (C22.2 No. 5) configurations & performance capabilities as a Molded Case Circuit  
Breaker.  
E SERIES TABLE A : UL489 LISTED BRANCH CIRCUIT BREAKERS  
VOLTAGE  
INTERRUPTING  
CURRENT RATING  
FULL LOAD AMPS  
HIGH  
INTERRUPTING  
CAPACITY  
(AMPS)  
CAPACITY (AMPS)  
CIRCUIT  
CONFIGURATION  
MAX.  
RATING  
FREQUENCY  
PHASE  
WITHOUT BACKUP  
FUSE  
80  
125  
125  
120  
240  
DC  
DC  
DC  
50 / 60  
50 / 60  
50 / 60  
50 / 60  
50 / 60  
50 / 60  
50 / 60  
---  
---  
---  
1
1
1
1
1
1
3
0.10 - 100  
0.10 - 100  
101 - 125  
101 - 125  
0.10 - 30  
31 - 100  
0.10 - 30  
31 - 100  
101 - 125  
0.10 - 100  
5,000  
5,000  
10,000  
10,000  
5,000  
5,000  
5,000  
5,000  
10,000  
5,000  
50,000  
10,000  
---  
---  
10,000  
SERIES  
240  
120 / 240  
120 / 240  
120 / 240  
240  
10,000  
---  
---  
---  
Table B: Lists UL Recognized & CSA Accepted configurations & performance capabilities as a Component Supplementary  
Protector.  
E -SERIES TABLE B: COMPONENT SUPPLEMENTARY PROTECTORS  
VOLTAGE  
CURRENT RATING  
SHORT CIRCUIT CAPACITY (AMPS)  
APPLICATION CODES  
UL/CSA  
CIRCUIT  
CONFIGURATION  
MAX.  
RATING  
FULL LOAD  
AMPS  
GENERAL  
PURPOSE AMPS  
FREQUENCY  
PHASE  
UL  
CSA  
WITH BACKUP  
FUSE3  
WITHOUT  
BACKUP FUSE  
125  
125  
150  
DC  
DC  
DC  
DC  
DC  
50 / 60  
50 / 60  
50 / 60  
---  
---  
---  
---  
---  
1
0.02 - 100  
---  
---  
0.02 - 100  
0.02 - 100  
---  
0.02 - 100  
0.02 - 100  
---  
101 - 120  
0.02 - 125  
---  
---  
---  
---  
---  
---  
---  
---  
10,000  
---  
10,000  
10,000  
10,000  
10,000  
---  
5,000  
5,000  
5,000  
5,000  
5,000  
5,000  
5,000  
---  
5,000  
---  
---  
---  
---  
TC1,2, OL1, U1 TC1,2, OL1, U1  
TC1,2, OL0, U1 TC1,2, OL0, U1  
TC1, OL0, U3 TC1, OL0, U3  
TC1,2, OL1, U1 TC1,2, OL1, U1  
TC1,2, OL1, U1 TC1,2, OL1, U1  
TC1,2, OL0, U1 TC1,2, OL0, U1  
TC1,2, OL1, U1 TC1,2, OL1, U1  
TC1,2, OL1, C1 TC1,2, OL1, C1  
TC1,2, OL1, U1 TC1,2, OL1, U1  
TC1,2, OL1, C1 TC1,2, OL1, C1  
TC1,2, OL1, C1 TC1,2, OL1, C1  
TC1,2, OL1, C1 TC1,2, OL1, C1  
TC1,2, OL1, C1 TC1,2, OL1, C1  
TC1, OL0, U3 TC1, OL0, U3  
160  
150 / 300  
120 / 240  
240  
---  
SERIES &  
SHUNT  
0.02 - 100  
---  
---  
1
1
250  
277  
50 / 60  
1
0.02 - 100  
---  
480  
480 1  
600  
600 2  
125  
160  
240  
277  
480  
600  
50 / 60  
50 / 60  
50 / 60  
DC  
1 & 3  
1 & 3  
1 & 3  
---  
0.02 - 100  
0.02 - 50  
0.02 - 100  
---  
---  
---  
---  
0.02 - 125  
5,000  
DC  
DC  
50 / 60  
50 / 60  
50 / 60  
50 / 60  
---  
---  
1
1
1 & 3  
1 & 3  
0.02 - 120  
0.02 - 100  
0.02 - 100  
0.02 - 100  
0.02 - 100  
0.02 - 100  
Table B Notes:  
1
2
3
Per pole opposite polarity rating - Delta Configuration.  
4 Poles connected in series  
Requires branch circuit backup with a UL Listed Type K5 or RK5 fuse  
rated 15A minimum and no more than 4 times full load amp rating and  
not to exceed 225A.  
SWITCH  
ONLY  
60 Johnson Avenue • Plainville, CT 06062–1177 • Phone: (860) 793–9281 • Fax: (860) 793–9231  
Email: sales@carlingtech.com • www.carlingtech.com  
|
4
E-Series Circuit Breaker - General Specifications  
Electrical Tables  
Table C: Lists UL Recognized, CSA Accepted and VDE Certified configurations and performance capabilities as a Component  
Supplementary Protector.  
E -SERIES TABLE C: COMPONENT SUPPLEMENTARY PROTECTORS WITH VDE  
VOLTAGE  
CURRENT RATING  
SHORT CIRCUIT CAPACITY (AMPS)  
UL/CSA VDE (Icn)  
APPLICATION CODES  
CIRCUIT  
CONFIGURATION  
MAX.  
RATING  
CONSTRUCTION NOTES  
WITHOUT  
BACKUP  
FUSE  
WITHOUT  
BACKUP  
FUSE  
FREQUENCY  
PHASE  
FULL LOAD AMPS  
UL  
CSA  
WITH BACKUP  
FUSE1  
125  
240  
DC  
---  
0.1 - 100  
0.1 - 100  
---  
5,000  
5,000  
TC1,2, OL1, U1 TC1,2, OL1, U1  
1 or 2 Poles  
1 - 5 Poles. Up to 4  
SERIES &  
SHUNT  
50 / 60  
1 & 3  
---  
5,000  
5,000  
TC1,2, OL1, U1 TC1,2, OL1, U1 Current Poles, 1 Voltage  
Pole  
2 - 5 Poles. Up to 4  
TC1,2, OL1, C1 TC1,2, OL1, C1 Current Poles, 1 Voltage  
Pole  
415  
50 / 60  
1 & 3  
0.1 - 100  
10,000  
---  
4,000  
---  
125  
240  
415  
DC  
50 / 60  
50 / 60  
0.1 - 125  
0.1 - 100  
0.1 - 100  
SWITCH ONLY  
1 & 3  
1 & 3  
Table C Notes:  
1
Requires branch circuit backup with a UL LISTED Type K5 or RK5 fuse rated 15A minimum and no more than 4  
times full load amp rating and not to exceed 225 amps.  
Table D: Lists UL Recognized, CSA Accepted configurations and performance capabilities as Protectors, Supplementary for  
Marine Electrical and Fuel Systems (Guide PEQZ2, File E75596). Ignition Protected per UL 1500. UL Classified Small Craft  
Electrical Devices, Marine in accordance with ISO 8846 (Guide UZMK, File MQ1515) as Marine Supplementary Protectors.  
E SERIES TABLE D : UL1500 (Marine Ignition Protection)  
VOLTAGE  
SHORT CIRCUIT  
CURRENT RATING  
FULL LOAD AMPS  
APPLICATION CODES  
CAPACITY (AMPS)  
CIRCUIT  
CONFIGURATION  
MAX.  
RATING  
FREQUENCY  
PHASE  
WITHOUT BACKUP  
FUSE  
UL  
CSA  
65  
125  
250  
DC  
50 / 60  
50 / 60  
---  
1
1
0.02 - 100  
0.02 - 100  
0.02 - 100  
5,000  
1,500  
1,500  
TC1,2,OL1,U1 TC1,2,OL1,U1  
TC1,2,OL1,U1 TC1,2,OL1,U1  
TC1,2,OL1,U1 TC1,2,OL1,U1  
SERIES  
60 Johnson Avenue • Plainville, CT 06062–1177 • Phone: (860) 793–9281 • Fax: (860) 793–9231  
Email: sales@carlingtech.com • www.carlingtech.com  
|
E-Series Handle UL Recognized – Ordering Scheme  
5
E A 2 – B 0 – 24 – 450 – 1 2 A – C B  
8
9
10  
Mounting/  
Barriers  
11  
12  
Agency  
1
2
3
4
5
6
7
Terminal  
Actuator  
Color  
Maximum  
Series  
Actuator  
Poles  
Circuit  
Auxiliary  
Switch  
Frequency  
& Delay  
Current Rating  
Application Approval  
Rating  
8 TERMINAL12  
1 SERIES  
BACK CONNECTED (FRONT MOUNTED ONLY)  
MAX. RATING  
50 A  
E
19  
29  
A9  
B9  
10-32 Stud (All Terminals)  
1/4-20 Stud (All Terminals)  
M5 Stud (Line & Load)  
M6 Stud (Line & Load)  
120 A  
50 A  
100 A  
2 ACTUATOR  
A
Handle, one per pole  
FRONT CONNECTED (BACK MOUNTED ONLY)  
MAX. RATING  
310  
C11  
4
Box Wire Connector (Line & Load)  
Box Wire Connector w/ Pressure Plate (Line & Load)  
10-32 Screw (Line & Load)  
100 A  
100 A  
50 A  
3 POLES1  
1
One  
Two  
3
4
Three  
Four  
5
6
Five  
Six  
2
D
5
M5 Screw (Line & Load)  
10-32 “Bus-Type” Screw (Line), 10-32 Screw (Load)  
M5 “Bus-Type” Screw (Line), 10-32 Screw (Load)  
10-32 “Bus-Type” Screw (Line), Box Wire Connector (Load)  
10-32 “Bus-Type” Screw (Line), Box Wire Connector  
w/ Pressure Plate (Load)  
1/4-20 Screw (Line & Load)  
M6 Screw (Line & Load)  
1/4-20 “Bus-Type” Screw (Line), 1/4-20 Screw (Load)  
M6 “Bus-Type” Screw (Line), M6 Screw (Load)  
1/4-20 “Bus-Type” Screw (Line), Box Wire Connector (Load) 100 A  
1/4-20 “Bus-Type” Screw (Line), Box Wire Connector  
50 A  
50 A  
50 A  
100 A  
E
4 CIRCUIT2  
610  
F11  
A3  
B
Switch Only no coil  
E
F
G
Shunt Trip voltage  
(
)
)
)
(
)
)
)
(
(
Series Trip current  
Series Trip voltage  
Relay Trip current  
100 A  
100 A  
100 A  
100 A  
100 A  
(
(
C
Relay Trip voltage  
7
G
8
( )  
D
Shunt Trip current  
H
5 AUXILIARY SWITCH4  
910  
J11  
0
2
3
4
without Auxiliary Switch  
S.P.D.T. 0.110 Q.C. Terminals  
S.P.D.T. 0.139 Solder Lug  
S.P.D.T. 0.110 Q.C. Terminals  
(Gold Contacts)  
6
7
S.P.D.T. 0.110 Q.C. Terminals  
S.P.D.T. 0.110 Q.C. Terminals  
(Gold Contacts)  
S.P.D.T. 0.187 Q.C. Terminals  
S.P.D.T. 0.187 Q.C. Terminals  
w/ Pressure Plate (Load)  
100 A  
8
9
9 ACTUATOR COLOR & LEGEND13  
Acuator Color  
White  
Legend Color  
Black  
I-O  
A
C
F
H
K
M
P
ON-OFF  
Dual  
B
D
G
J
1
2
3
4
5
6
7
8
6 FREQUENCY & DELAY  
34  
36  
62  
64  
66  
72  
74  
76  
926  
946  
DC, 50/60Hz Medium  
DC, 50/60Hz Long  
50/60Hz Short, Hi-Inrush  
50/60Hz Medium, Hi-Inrush  
50/60Hz Long, Hi-Inrush  
DC, Short,Hi-Inrush  
DC,Medium, Hi-Inrush  
DC, Long, Hi-Inrush  
DC, 50/60Hz Short, Hi-Inrush  
DC, 50/60Hz Medium,  
Hi-Inrush  
Black  
White  
033  
105  
12  
14  
16  
205  
22  
24  
26  
30  
32  
DC 50/60Hz, Switch Only  
DC Instantaneous  
DC Short  
Red  
White  
Green  
Blue  
Yellow  
Gray  
White  
White  
L
DC Medium  
DC Long  
50/60Hz Instantaneous  
50/60Hz Short  
50/60Hz Medium  
50/60Hz Long  
Black  
N
Q
S
Black  
Orange  
Black  
R
10 MOUNTING/BARRIERS  
BACK CONNECTED (FRONT MOUNTED ONLY)  
DC, 50/60Hz Instantaneous  
DC, 50/60Hz Short  
966  
DC, 50/60Hz Long, Hi-Inrush  
Mounting Inserts  
6-32  
A
B
ISO M3  
7 CURRENT RATING (AMPERES)7  
FRONT CONNECTED (BACK MOUNTED ONLY)14  
CODE AMPERES  
Back Mounting Foot Type Front Mounting Inserts (Optional Use)  
020 0.020  
025 0.025  
030 0.030  
035 0.035  
040 0.040  
045 0.045  
050 0.050  
055 0.055  
060 0.060  
065 0.065  
070 0.070  
075 0.075  
080 0.080  
085 0.085  
090 0.090  
090 0.095  
210 0.100  
215 0.150  
220 0.200  
225 0.250  
230 0.300  
235 0.350  
240 0.400  
245 0.450  
250 0.500  
255 0.550  
260 0.600  
265 0.650  
270 0.700  
275 0.750  
280 0.800  
285 0.850  
290 0.900  
295 0.950  
410 1.000  
512 1.250  
415 1.500  
517 1.750  
420 2.000  
522 2.250  
425 2.500  
527 2.750  
430 3.000  
435 3.500  
440 4.000  
445 4.500  
450 5.000  
455 5.500  
460 6.000  
465 6.500  
470 7.000  
475 7.500  
480 8.000  
485 8.500  
490 9.000  
495 9.500  
610 10.000  
710 10.500  
611 11.000  
711 11.500  
612 12.000  
712 12.500  
613 13.000  
614 14.000  
615 15.000  
616 16.000  
617 17.000  
618 18.000  
620 20.000  
622 22.000  
624 24.000  
625 25.000  
630 30.000  
635 35.000  
640 40.000  
650 50.000  
660 60.000  
670 70.000  
680 80.000  
690 90.000  
810 100.000  
811 110.000  
812 120.000  
9128 125.000  
C
D
E
F
Short  
Short  
Long  
Long  
6-32  
ISO M3  
6-32  
ISO M3  
11 MAXIMUM APPLICATION RATING15  
A
65 VDC, 120 A  
G16 600 VAC, 100 A  
B
125 VDC, 120 A  
120/240 VAC, 100 A  
240 VAC, 100 A  
277/480 VAC, 100 A  
277 VAC, 100 A  
H16  
J16  
L16  
T
480 VAC, 100 A  
C
415 VAC, 100 A  
D
160 VDC, 100 A  
E16  
F
125 VDC/240 VAC, 100 A  
W16 125 VDC/415 VAC, 100 A  
12 AGENCY APPROVAL  
B
D
UL 1077 / UL508 Recognized & CSA Accepted  
UL 1077 Recognized, CSA Accepted, & VDE Certified  
4
5
Auxiliary Switch available on Switch Only and Series Trip units. On multi-pole units, only  
one auxiliary switch is normally supplied mounted in the extreme right pole. Back mounted  
units require special mounting provisions when auxiliary switch is specified. VDE approval  
on Auxilary Switch Codes 0,2,3 & 4 only.  
Voltage Trip Coils are not rated for continuous duty. Available only with Frequency & Delay  
Codes 10 & 20. Series Trip construction with a voltage coil s VDE approved only if tied to  
a protected pole.  
Frequency & Delay Codes 92,94 & 96 are not VDE Certified.  
Current Coil Ratings 0.100 - 100 ams are VDE Certified.  
OR VOLTAGE COIL (MIN. TRIP RATING, VOLTS)5  
A06 6 DC, 5 DC  
A12 12 DC, 10 DC  
A18 18 DC, 15 DC  
A24 24 DC, 20 DC  
A32 32 DC, 25 DC  
A48 48 DC, 40 DC  
A65 65 DC, 55 DC  
J48 48 AC, 40 AC  
J65 65 AC, 55 AC  
K20 120 AC, 65 AC  
L40 240 AC, 130 AC  
B25 125 DC, 100 DC  
J06  
6 AC, 5 AC  
J12 12 AC, 10 AC  
J18 18 AC, 15 AC  
J24 24 AC, 20 AC  
6
7
8
9
125 A rating (Code 912) available as a Switch Only (Circuit Code A), rated 125 VDC (Code B).  
An Anti-Flash Over Barrier is supplied between poles on multi-pole units with 10-32 (Terminal  
Code 1). 1/4-20 (Code 2), M5 (Code A), and M6 (Code B) terminals per UL requirement.  
Notes:  
10 Box Wire Connector will accept #14 through 0 AWG. copper wire or #12 through 0 AWG.  
aluminum wire.  
11 Box Wire Connector with Pressure Plate for stranded wire, consult factory for details.  
12 Terminal Codes A,B,D,E,G & H are not VDE Certified.  
1
VDE approval on 1-5 poles only. Standard multi-pole units identical poles except when  
specifying auxiliary switch - (see Note 4). For mixed ratings, consult factory.  
Switch Only & Series Trip construction available w/either front or back connected terminals.  
Shunt construction available w/back connected terminals, (Terminal Codes 1 & 2) only.  
Circuit Codes B,C & D are VDE approved.  
Switch Only construction: 30 amps or less select Current Rating Code 630; 31-70 amps,  
select Current Rating code 670; 71-100 amps, select Current Rating Code 810; 101-125  
amps Select Current Rating Code 912. Switch Only is VDE approved only if tied to a  
protected pole.  
2
13 VDE approvals require Dual (I-O, ON-OFF) or I-O markings on all handles.  
14 Back Mounted breakers can also be front mounted by utilizing the proper front panel mounting  
inserts normally supplied. However, terminal connections must be made prior to mounting.  
15 Application ratings B,D,J,T & W are available with VDE.  
3
16 415, 480 & 600 VAC ratings require 3 or 4 pole break 3Ø and 2 pole break 1Ø.  
60 Johnson Avenue • Plainville, CT 06062–1177 • Phone: (860) 793–9281 • Fax: (860) 793–9231  
Email: sales@carlingtech.com • www.carlingtech.com  
|
6
E-Series Handle UL Listed – Ordering Scheme  
E A 2 – B 0 – 24 – 450 – 1 2 A – C C  
8
9
10  
Mounting/  
Barriers  
11  
12  
Agency  
1
2
3
4
5
6
7
Terminal  
Actuator  
Color  
Maximum  
Series  
Actuator  
Poles  
Circuit  
Auxiliary  
Switch  
Frequency  
& Delay  
Current Rating  
Application Approval  
Rating  
8 TERMINAL7  
1 SERIES  
BACK CONNECTED (FRONT MOUNTED ONLY)  
MAX. RATING  
50 A  
125 A  
MAX. RATING  
E
18  
28  
10-32 Stud (All Terminals)  
1/4-20 Stud (All Terminals)  
2 ACTUATOR  
FRONT CONNECTED (BACK MOUNTED ONLY)  
39  
C10  
4
Box Wire Connector (Line & Load)  
Box Wire Connector w/ Pressure Plate (Line & Load)  
10-32 Screw (Line & Load)  
100 A  
100 A  
50 A  
50 A  
A
Handle, one per pole  
3 POLES1  
5
10-32 “Bus-Type” Screw (Line), 10-32 Screw (Load)  
69  
F10  
10-32 “Bus-Type” Screw (Line), Box Wire Connector (Load)  
10-32 “Bus-Type” Screw (Line), Box Wire Connector  
w/ Pressure Plate (Load)  
100 A  
1
2
One  
Two  
3
4
Three  
Four  
5
6
Five  
Six  
100 A  
125 A  
100 A  
7
1/4-20 Screw (Line & Load)  
1/4-20 “Bus-Type” Screw (Line), 1/4-20 Screw (Load)  
1/4-20 “Bus-Type” Screw (Line), Box Wire Connector (Load) 100 A  
1/4-20 “Bus-Type” Screw (Line), Box Wire Connector  
4 CIRCUIT2  
8
B
Series Trip current  
C3  
Series Trip voltage  
(
)
(
)
99  
J10  
w/ Pressure Plate (Load)  
100 A  
5 AUXILIARY SWITCH4  
0
2
3
4
without Auxiliary Switch  
S.P.D.T. 0.110 Q.C. Terminals  
S.P.D.T. 0.139 Solder Lug  
S.P.D.T. 0.110 Q.C. Terminals  
(Gold Contacts)  
6
7
S.P.D.T. 0.110 Q.C. Terminals  
S.P.D.T. 0.110 Q.C. Terminals  
(Gold Contacts)  
S.P.D.T. 0.187 Q.C. Terminals  
S.P.D.T. 0.187 Q.C. Terminals  
9 ACTUATOR COLOR & LEGEND12  
Acuator Color  
White  
Legend Color  
Black  
ON-OFF  
Dual  
8
9
B
D
G
J
1
2
3
4
5
6
7
8
Black  
White  
Red  
White  
Green  
Blue  
White  
6 FREQUENCY & DELAY  
36  
62  
64  
66  
72  
74  
76  
926  
946  
DC, 50/60Hz Long  
White  
L
105  
12  
14  
16  
205  
22  
24  
26  
30  
32  
34  
DC Instantaneous  
DC Short  
DC Medium  
DC Long  
50/60Hz Instantaneous  
50/60Hz Short  
50/60Hz Medium  
50/60Hz Long  
DC, 50/60Hz Instantaneous  
DC, 50/60Hz Short  
DC, 50/60Hz Medium  
50/60Hz Short, Hi-Inrush  
50/60Hz Medium, Hi-Inrush  
50/60Hz Long, Hi-Inrush  
DC, Short,Hi-Inrush  
DC,Medium, Hi-Inrush  
DC, Long, Hi-Inrush  
DC, 50/60Hz Short, Hi-Inrush  
DC, 50/60Hz Medium,  
Hi-Inrush  
Yellow  
Gray  
Black  
N
Q
S
Black  
Orange  
Black  
10 MOUNTING/BARRIERS  
BACK CONNECTED (FRONT MOUNTED ONLY)  
Mounting Inserts  
6-32  
A
B
966  
DC, 50/60Hz Long, Hi-Inrush  
ISO M3  
FRONT CONNECTED (BACK MOUNTED ONLY)11  
Back Mounting Foot Type Front Mounting Inserts (Optional Use)  
C
D
E
F
Short  
Short  
Long  
Long  
6-32  
ISO M3  
6-32  
7 CURRENT RATING (AMPERES)7  
CODE AMPERES  
ISO M3  
020 0.020  
025 0.025  
030 0.030  
035 0.035  
040 0.040  
045 0.045  
050 0.050  
055 0.055  
060 0.060  
065 0.065  
070 0.070  
075 0.075  
080 0.080  
085 0.085  
090 0.090  
090 0.095  
210 0.100  
215 0.150  
220 0.200  
225 0.250  
230 0.300  
235 0.350  
240 0.400  
245 0.450  
250 0.500  
255 0.550  
260 0.600  
265 0.650  
270 0.700  
275 0.750  
280 0.800  
285 0.850  
290 0.900  
295 0.950  
410 1.000  
512 1.250  
415 1.500  
517 1.750  
420 2.000  
522 2.250  
425 2.500  
527 2.750  
430 3.000  
435 3.500  
440 4.000  
445 4.500  
450 5.000  
455 5.500  
460 6.000  
465 6.500  
470 7.000  
475 7.500  
480 8.000  
485 8.500  
490 9.000  
495 9.500  
610 10.000  
710 10.500  
611 11.000  
711 11.500  
612 12.000  
712 12.500  
613 13.000  
614 14.000  
615 15.000  
616 16.000  
617 17.000  
618 18.000  
620 20.000  
622 22.000  
624 24.000  
625 25.000  
630 30.000  
635 35.000  
640 40.000  
650 50.000  
660 60.000  
670 70.000  
680 80.000  
690 90.000  
810 100.000  
811 110.000  
812 120.000  
9128 125.000  
11 MAXIMUM APPLICATION RATING  
1
120 VAC  
B
125 VDC, 120 A  
120/240 VAC, 100 A  
240 VAC, 100 A  
C13  
D
12 AGENCY APPROVAL  
C
F
UL 489 Listed & CSA Certified  
UL 489 Listed, CSA Certified, & VDE Certified  
Notes:  
1
Standard multi-pole units identical poles except when specifying auxiliary switch -  
(see Note 4). For mixed ratings, consult factory. VDE Certification on 1-5 poles only.  
Series Trip construction available w/either front or back connected terminals.  
Series Trip construction with a voltage coil is not available as a single pole unit and must be  
tied to a protected pole.  
On multi-pole units, only one auxiliary switch is normally supplied mounted in the extreme  
right pole per Figure A. Back mounted units require special mounting provisions when  
auxiliary switch is specified. VDE Certification on auxilary switch codes 0, 2, 3 & 4 only.  
Voltage Trip Coils are not rated for continuous duty. Available only with Frequency & Delay  
Codes 10 & 20.  
Frequency & Delay Codes 92, 94 & 96 are not VDE Certified.  
Current Ratings under 0.100 amps are not VDE Certified .  
2
3
4
OR VOLTAGE COIL (MIN. TRIP RATING, VOLTS)5  
A06 6 DC, 5 DC  
A12 12 DC, 10 DC  
A18 18 DC, 15 DC  
A24 24 DC, 20 DC  
A32 32 DC, 25 DC  
A48 48 DC, 40 DC  
A65 65 DC, 55 DC  
J48 48 AC, 40 AC  
J65 65 AC, 55 AC  
K20 120 AC, 65 AC  
L40 240 AC, 130 AC  
B25 125 DC, 100 DC  
5
J06  
6 AC, 5 AC  
6
7
8
J12 12 AC, 10 AC  
J18 18 AC, 15 AC  
J24 24 AC, 20 AC  
An Anti-Flash Over Barrier is supplied between poles on multi-pole units with 10-32 Stud  
(Terminal Code 1) or 1/4-20 Stud (Code 2) terminals per UL requirement.  
Box Wire Connector will accept #14 through 0 AWG. copper wire or #12 through 0 AWG.  
aluminum wire.  
9
10 Box Wire Connector with Pressure Plate for stranded wire, consult factory for details.  
11 Back Mounted breakers can also be front mounted by utilizing the proper front panel mouning  
inserts normally supplied. However, terminal connections must be made prior to mounting.  
12 VDE Certification requires dual (I-O , ON-OFF) markings on all handles.  
13 Not available with VDE Certification.  
60 Johnson Avenue • Plainville, CT 06062–1177 • Phone: (860) 793–9281 • Fax: (860) 793–9231  
Email: sales@carlingtech.com • www.carlingtech.com  
|
E-Series Handle – Circuit & Terminal Diagrams  
7
Notes:  
1
2
3
4
All dimensions are in inches [millimeters].  
Tolerance ±.020 [.51] unless otherwise specified.  
0-50 amps: 10-32 & M5 Studs .625±.062/15.88±1.574 long.  
51-120 amps: 1/4-20 & M6 Studs .750±.062/19.05±1.574 long.  
60 Johnson Avenue • Plainville, CT 06062–1177 • Phone: (860) 793–9281 • Fax: (860) 793–9231  
Email: sales@carlingtech.com • www.carlingtech.com  
|
8
E-Series Handle (Back Connected) – Form & Fit Drawings  
Notes:  
1
2
1/4 -20 stud terminal in Series Trip circuit configuration shown.  
A 3” min spacing must be provided between the circuit breaker arc venting area  
of back connected E-Series circuit breaker and grounded obstructions.  
All dimensions are in inches [millimeters].  
3
4
5
Tolerance ±.020 [.51] unless otherwise specified.  
Circuit breakers must be mounted on vertical surface.  
60 Johnson Avenue • Plainville, CT 06062–1177 • Phone: (860) 793–9281 • Fax: (860) 793–9231  
Email: sales@carlingtech.com • www.carlingtech.com  
|
E-Series Handle (Front Connected) – Form & Fit Drawings  
9
Notes:  
1
2
3
4
All dimensions are in inches [millimeters].  
Tolerance ±.020 [.51] unless otherwise specified.  
Box wire connector terminal in Series Trip circuit configuration shown.  
Circuit breakers must be mounted on vertical surface.  
REV_CB_E_0812  
60 Johnson Avenue • Plainville, CT 06062–1177 • Phone: (860) 793–9281 • Fax: (860) 793–9231  
Email: sales@carlingtech.com • www.carlingtech.com  

相关型号:

EA2-B0-24-610-4CA-CB

Magnetic Circuit Breaker,
Carling Techn

EA2-B0-24-615-2DA-DC

Magnetic Circuit Breaker,
Carling Techn

EA2-B0-24-625-2DA-DC

Magnetic Circuit Breaker,
Carling Techn

EA2-B0-24-630-2DA-DC

Magnetic Circuit Breaker,
Carling Techn

EA2-B0-24-650-32A-DB

Magnetic Circuit Breaker,
Carling Techn

EA2-B0-24-670-73C-CC

Magnetic Circuit Breaker,
Carling Techn

EA2-B0-26-450-32E-HB

Magnetic Circuit Breaker,
Carling Techn

EA2-B0-26-475-32F-FB

Magnetic Circuit Breaker,
Carling Techn

EA2-B0-26-610-1DA-EB

Magnetic Circuit Breaker,
Carling Techn

EA2-B0-26-615-22A-DF

Magnetic Circuit Breaker,
Carling Techn

EA2-B0-26-625-22A-DF

Magnetic Circuit Breaker,
Carling Techn

EA2-B0-26-670-32E-GB

Magnetic Circuit Breaker,
Carling Techn